Measuring AC supply voltage May 2016

With the JeeLabs Energy Monitor prototype hooked up in the meter cabinet, it’s now very easy to explore things a bit. One interesting test is to look at the analog signal from the AC power supply + divider, which is connected to pin PA0.

Here is some code which samples that signal and prints it out until a key is pressed:

: a1 +adc begin pa0 adc . key? until ;
a1 4029 4031 4030 4030 [...] 1268 1343 1763 2330  ok.

The ADC is initialised, and then we acquire a value, print it, and loop until some key is pressed. The readings are easily copied to a spreadsheet and graphed:

Some observations:

The current polled ADC acquisition code itself is very fast. It’s easy to measure this:

: a2 micros pa0 adc micros nip swap - . ;  ok.
a2 41  ok.

So it takes 41 µs to acquire one ADC sample (less actually, the micros code has some overhead). To improve on this, we can first acquire samples in a quick loop, and then print them out:

4000 buffer: adata  ok.
: a3 1000 0 do pa0 adc i cells adata + ! loop ;  ok.
: a4 +adc micros a3 micros swap - . ;  ok.
: a5 1000 0 do i cells adata + @ . loop ;  ok.
a4 32915  ok.
a5 1333 1334 1334 [...] 4026 4028 4027  ok.

Which means that we’ve captured 33 ms of data, i.e. more than one full 50 Hz cycle:

Both half-wave captures consist of 338 readings, with 269 readings in between, when the ADC returns 4030 or 4031. Which means that the zero crossings are indeed included in our data, and that there is enough information to reconstruct a full sine wave for CT power calculations later.

Note that the sine wave has somewhat flattened peaks and there also appears to be some noise.

These readings were taken with a µC running at 8 MHz, which gives enough resolution for now. At 72 MHz, a2 reports 6 µs and a4 reports 4949 µs - this translates to a polled ADC acquisition rate of over 200,000 samples per second. The flip side is that at this higher rate we can only capture some 5 ms with a 1000-entry buffer, considerably less than a full 50 Hz AC cycle:

For tests, the polled approach is fine - and very convenient, given the interactive command-line access provided by the ESP-Link - but the acquisition rate will not be constant due to occasional interrupts, and the µC would be tied up most of the time, which is clearly not very practical.

The solution is to use DMA-based ADC acquisition. Then, we only need to deal with acquired data in large chunks. The STM32F103 µC’s DMA hardware has two nice interrupts for this: when the buffer is half full, and when it reaches the end and acquisition starts over at the beginning.

Let’s plan ahead a bit and consider the rates and time + memory resources needed:

Even if our calculations take more than 32 ms, this would be ok: we could simply ignore some acquisition cycles. The only constraint is that the buffered data needs to be processed (or moved out of the way) before the DMA engine overwrites it with new data, i.e. within 32 ms.

The beauty of DMA is that it completely frees the CPU. It “only” has to deal with ≈ 30 interrupts per second, with all ADC values acquired exactly 40 µs apart and stored in the DMA buffer.

There is still plenty of work to do… such as dealing with phase and finding those zero crossings.